The menus are currently in german. If there is a high demand, i will make an english version.
The Software
The menu is controlled by three keys (alternative an incremental interface)
Remote display by a second AVR-Control si also possible.
Tk = Boiler temperature
Ta = Outside temperature
Ts = Setpoint - boiler temperature (regulating value)
* = Symbol for operating mode
Status-Menu
Do 15:31 * 25%
Ta=+ 3° Tk=+ 50°C
Day and time .
Operating-mode: Sun=Day, full circle = Night, empty circle = Absent.
Up right: Gas consumption. Open gas ventile in percent of time of the day. (6h --> 25%)
In the 2. line the Outside and boiler temperature is shown.
The outside temp and the setpoint is shown alternately .
Keys:
- / + : Change menu
Enter : set time
Timer - Setup - Menu
WT *07:00 *08:00
1 *17:00 *22:00
Weekday (Mo - Fr, Sa, So and WT for Working days).
Timer time and operating mode as symbol.
4 timers are possible each day
Keys:
- / + : change weekday
Enter : change timer time(mit - / +)
The arror shows what to change
Timer setup
Mo 07:00 *
Mode Tag
Here the timer operating mode can be selected (Tag = Day, Nacht = Night, Abwesend = Absent, Deaktiv = deactivate this timer)
Keys:
- / + : change value
Enter: Okay
Timer groups (Schalt - Gruppen) Menu
Two sets of timers are present .(e.G. Holyday). Keys: - / + Select group
Enter : exit
Temperature courves (Kennlinien) - Menu
* 79° bei -10°
30° bei +21°
These are the two edge points of each operating mode.
79°C Boiler at (bei) -10°C.
Use the windows tool to visualize. Keys:
- / + : change mode
Enter : change values
Circulation pump (Wasserpumpen) - Menu
Pumpe aus *
Nacht Tk < +33°C
This is the boiler temperature for switching the water pump.
Pumpe aus = pump off
To avoid switching off the pump in one operating point, you could set the temperature to a very high poin (e.g. 80°C)
Keys:
- / + : Change value
Enter: change mode
Consumption (Verbrauch) - Menü
Here the consumption of the last 5 days are shown .